Please note that the installations with multi manifolds above 2000 kg and up to 4000 kg shall have either water sprinkler system or gas monitoring system with local as well as remote alarm system and installation above 4000 kg to 8000 kg shall have both water sprinkler as well as gas monitoring system. Design Reference : IS 15325:2020 Design and Installation of Fixed Automatic Medium Velocity Water Spray System.